- PWM 방식과 인버터 방식을 사용한 시스템 에어컨의 성능평가에 대한 실험적 연구(난방저온 특성)
- ㆍ 저자명
- 김대훈,전용호,권영철,이윤수,문제명,홍주태
- ㆍ 간행물명
- 설비공학논문집
- ㆍ 권/호정보
- 2003년|15권 7호|pp.551-556 (6 pages)
- ㆍ 발행정보
- 대한설비공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
The present study concerns an experiment on the heating characteristics of a system air-conditioner (A/C) using PWM method or inverter method at low temperature con-ditions. The compressors used are digital scroll type and BLDC inverter type. Under the low outside temperature condition, -5$^{circ}C$, -1$0^{circ}C$, -15$^{circ}C$, heating capacities and COPs are mea-sured by the psychometric calorimeter using air enthalpy method. Also, outlet air temperatures at heating operation mode are measured at -5$^{circ}C$, -1$0^{circ}C$ and -15$^{circ}C$. Experimental results show that COPs of the system A/C using a PWM method are more effective than those of the inverter method at heating operation mode. Although the heater is on, COPs of PWM method are similar to those of BLDC inverter method. Moreover, the heating capacities of PWM method at -5$^{circ}C$, -1$0^{circ}C$ and -15$^{circ}C$ are larger about 10~20% and outlet air tempe-rature at -15$^{circ}C$ is larger about 10%, compared to the inverter method.