- R407C의 온도구배와 과열도가 증발기 성능에 미치는 영향
- ㆍ 저자명
- 김창덕,전창덕,이진호
- ㆍ 간행물명
- 설비공학논문집
- ㆍ 권/호정보
- 2003년|15권 10호|pp.852-859 (8 pages)
- ㆍ 발행정보
- 대한설비공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
R407C is considered as an alternative refrigerant of R22 for air conditioners. An experiment was carried out to investigate the characteristics of the evaporation heat transfer and pressure drop for refrigerant R407C flowing in a fin-and-tube heat exchanger used for commercial air-conditioning unit. The experimental data were useful in analyze the effects of the temperature glide and superheat for R407C. Test were conducted at the conditions of inlet refrigerant evaporation temperature of 7$^{circ}C$, inlet air relative humidity of 50%, and refrigerant mass fluxes varying from 150 to 250 kg/m$^2$s. Representative results show that the heat exchanger performance for R407C evaporation is significantly affected by the change of the flow pattern from two-phase to super-heated vapor flow.