- 이중외피 중공층의 열성능을 고려한 블라인드 위치 계획
- ㆍ 저자명
- 최동희,조재훈,석호태,여명석,김광우,Choi. Dong-Hee,Jo. Jae-Hun,Seok. Ho-Tae,Yeo. Myoung-Souk,Kim. Kwang-Woo
- ㆍ 간행물명
- 설비공학논문집
- ㆍ 권/호정보
- 2005년|17권 7호|pp.620-628 (9 pages)
- ㆍ 발행정보
- 대한설비공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
The blinds in the intermediate space are installed to block the direct solar radiation. As the blind divide the airflow of intermediate space into two, thermal performance of Double-Skin Facade (DSF) are affected by the blind position. Therefore blind position should be planed with careful consideration in order to maximize the thermal performance of DSF. In this study, CFD was peformed to analyze the effect of blind position in multistory-type DSF in variation of other DSF elements. The simulation results showed that the case with narrow depth of intermediate space and outlet on upper side of outer-facade, it is profitable to place blind as close as possible to the outer-facade. In the other cases, the blind should maintain 0.15 m distance from outer-facade.