In this study, we have investigated the effect of the solar power generation facilities on the power quality of interconnected solar power generation system. When the solar power generation facility was connected to the distribution system, whether the solar power generation is under operation or not, Peak factor of current was increased to 0.033[%], Frequency is deviated from $60{pm}0.2$[Hz] and also Short term flicker indication($P_{st}$) increased to 0.213[p.u.] compare with the disconnected situation. Harmonic current [%] in orders was 11.42[%] maximum under 11th orders and was 7.861[%] between 11th and 17th orders. These values were about 3 or 4 times compared with "the power system interconnection technique standards" at the same situation above. Therefore, we could confirmed that the solar power generation facility, when it was connected to the existing distribution system, made bad influence on the power qualities such as the peak factor of current, frequency regulation, short term flicker indication($P_{st}$) and harmonic current [%] in orders etc.