- 6.6 kV 케이블의 절연저항 측정을 위한 부하전류 및 온도 측정
- ㆍ 저자명
- 박용규,조영식,이관우,엄기홍,박대희,Park. Yong-Kyu,Cho. Young-Seek,Lee. Kwan-Woo,Um. Kee-Hong,Park. Dae-Hee
- ㆍ 간행물명
- 전기전자재료학회논문지
- ㆍ 권/호정보
- 2015년|28권 1호|pp.46-50 (5 pages)
- ㆍ 발행정보
- 한국전기전자재료학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
The cable degradation process is largely divided into three steps; Step 1 : Thermal degradation, Step 2 : Weibull degradation, Step 3 : Partial discharge. it is progress in step order. This article aims to explain the process of cable degradation using the method of insulation resistance and accordingly to compose and manufacture a system of measuring the life of electrical cable. Before measuring the insulation resistance, a system of measuring the temperature and current of cables was made, and the established system was installed for test on the site of a power plant to collect the measured data. The current sensor was used TFC30P80A-CL420, and temperature sensor was used the DK-1270 PT100 sensor as RTD sensor. When measured the temperature and the load current at the same position, was confirmed that in case of the load current value was high, also temperature value high. Therefore, the correlation between load currents and temperature was verified, and the analysis of diagnostic data was evaluated, which could be utilized in identifying the fault condition of cable systems.