- $SF_6$와 공기의 혼합기체중에서의 연면 코로나 방전
- ㆍ 저자명
- 전춘생,조기선,우호환
- ㆍ 간행물명
- 전기학회지= The Processing of the Institute of Electrical Engineers
- ㆍ 권/호정보
- 1977년|26권 6호|pp.78-85 (8 pages)
- ㆍ 발행정보
- 대한전기학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
This paper studies flashover voltage and surface corona loss of A.C and D.C in the mixed gas of air and SF$_{6}$ for solid insulators P.V.C, arcylic, glass and bakelite in two cases. In one case, those solids are covered with transformer oil and the other case, those solids are not covered with it. 1) The flashover voltage for each solids in SF$_{6}$ is more than three times compared with that in the air. The flashover voltage for P.V.C is the highest and then arcylic, glass, bakelite in a decreasing order. 2) The more the amount of SF$_{6}$ in the mixing ratio, the less corona loss. The P.V.C shows the least amount of corona loss and the bakelite the largest. 3) Compared with the corona loss of positive polarity and the negative polarity, the former has less corona loss than the latter. 4) The more the number of flashover discharge, the less insulation of each solids, but in case of bakelite, insulation almost vanishes after a couple of discharge. 5) When each insulator is covered with transformer oil, the flashover voltage generally increases and the corona loss decreases.eases.