- 변압기내 부분방전 탐지 및 위치검출
- Detection and Location of Partial Discharge in Transformers
- ㆍ 저자명
- 곽희노,김재철,황선주,권태원,윤용범
- ㆍ 간행물명
- 照明·電氣設備學會誌
- ㆍ 권/호정보
- 1992년|6권 4호|pp.53-59 (7 pages)
- ㆍ 발행정보
- 한국조명전기설비학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
This paper describes an instrument for the detection and geometric location of partial discharge (PD) source in transformers. This instrument measures electric current pulses and ultrasonic pulses simultaneously, counts the number of electrical pulses and determines the geometric location of PD in transformers. It was found that there is a relationship between partial discharge magnitude and pulse repetition rate when the applied test voltage and oil temperature were varied. Through the laboratory test using model transformer, it was clarified that this detector could be used for detecting and locating PD in the transformer.