- CFC 대체냉매를 사용한 핀-관 열교환기의 성능해석
- The Performance Analysis of the Fin-Tube Heat Exchanger Using CFC Alternative Refrigerant
- ㆍ 저자명
- 박희용,박경우,차재병
- ㆍ 간행물명
- 大韓機械學會論文集
- ㆍ 권/호정보
- 1993년|17권 9호|pp.2358-2372 (15 pages)
- ㆍ 발행정보
- 대한기계학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
In this study, the computer modeling for prediction of the performance of fin-tube heat exchanger using alternative refrigerant, HFC-134a was developed and the computer program for calculating the various properties of HFC-134a and the existing refrigerant CFC-12 and HCFC-22 was made. The heat exchanger modeling is based on a tube-by-tube approach, which is capable of analysis for the complex coil array. Performance of each tube is analyzed separately by considering the cross-flow heat transfer with external airstream and the appropriate heat and mass transfer relationships. A performance comparison according to the different refrigerants is provided using this developed model. As the result of this study, total heat transfer rate of evaporator and condenser using HFC-134a were found higher than that of using CFC-12 for the same operating conditions. When the mass flow rate of HFC-134a was less than CFC-12 about 18. 16%, the cooling capacities of evaporator were found to be the same.