- 핀끝이 절연되었다는 가정하에 삼각핀 해석에서의 오차
- Errors in the Triangular Fin Analysis under Assuming the Fin Tip is Insulated
- ㆍ 저자명
- 강형석,김성준
- ㆍ 간행물명
- 大韓機械學會論文集
- ㆍ 권/호정보
- 1994년|18권 7호|pp.1783-1788 (6 pages)
- ㆍ 발행정보
- 대한기계학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
A comparison of the temperature distributions along the wall and center of the fin and the heat loss from the fin, computed assuming the fin tip is insulated and assuming it is not insulated in a triangular fin, is performed by the two-dimensional forced analytic method. When the fin tip is not insulated, a comparison between forced analytic method and analytic method is made in the heat loss and temperature along the fin wall. The value of Biot number varies from 0.01 to 1.0. The root temperature and surrounding convection coefficients of the fin are assumed as a constant. The results are (1) the analysis on the triangular fin assuming the fin tip is insulated does not produce a good value as compared to that of not-insulated case as the non-dimensional fin length decreases and as the value of Biot number increases and (2) the errors between forced analytic method and analytic method are very small, but the former method is better for computer running time and accuracy.