- 부하차단시험에 의한 서인천복합화력 발전기.제어계의 모델링 및 검증
- ㆍ 저자명
- 최경선,문영환,김동준,추진부,류승헌,권태원
- ㆍ 간행물명
- 電氣學會論文誌
- ㆍ 권/호정보
- 1996년|45권 4호|pp.501-510 (10 pages)
- ㆍ 발행정보
- 대한전기학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
The gas-turbine generator of Seo-Incheon combined-cycle plant was tested for derivation of a model for dynamic analysis. Load rejection and AVR step test was performed to get the dynamic response of generator. The parameters of generator/control system model were determined by these measured data. No-load saturation test was performed for the saturation characteristics of the generator under steady state. V-curve test was also performed so as to find exact generator parameters. Q-axis parameters of generator was derived by measuring power angle. AVR and governor constants have been tuned by their oscillatory period and setting time characteristics. The derived parameters of generator control system is verified by one-machine infinite bus system simulation. (author). 7 refs., 20 figs., 5 tabs.