- 해수냉각시스템 성능에 미치는 냉매배관길이의 영향
- ㆍ 저자명
- 윤정인,조영제,Yun. Jeong-In,Jo. Yeong-Je
- ㆍ 간행물명
- 한국어업기술학회지
- ㆍ 권/호정보
- 1998년|34권 3호|pp.346-351 (6 pages)
- ㆍ 발행정보
- 한국어업기술학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
The purpose of this study is analyzing the performance of sea water cooling system under various refrigerant pipe length. In sea water cooling system, the increase of refrigerant pipe length cause increases of pressure drops. These pressure drops cause fresh gas in liquid pipe and increase specific volume in gas pipe outlet, so sea water cooling system capacity is decreased by decrease of refrigerant mass flow rate. Sea water cooling system capacity in refrigerant pipe length 70m is decreased more than 30% when compared with pipe length 10m and the decrease of the coefficient of performance is nearly 20%.