- 관외 빙착형 빙축열시스템의 운전방식에 따른 최소용량 비교
- ㆍ 저자명
- 이대영,정성훈,강병하
- ㆍ 간행물명
- 空氣 調和·冷凍 工學 論文集
- ㆍ 권/호정보
- 1999년|11권 3호|pp.401-413 (13 pages)
- ㆍ 발행정보
- 대한설비공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
An ice storage cooling facility with cooling capacity of 150㎾ has been constructed for the purpose of developing optimal design and control strategy for an ice storage system. As the first step to this purpose, a computer program has been developed to simulate the operation of the ice storage system and examined precisely by comparing the results with those measured from the test facility. With the simulation program verified from the comparison, a design procedure has been developed to determine the minimum capacity required for each operation strategy available commercially. It is shown that the minimum sizes of the chiller and the storage tank are strongly dependent on the control strategy, i.e., chiller priority or storage priority, but less affected by the arrangement method, i.e., chiller upstream or chiller downstream.