- 배전용 폴리머애자의 현장열화 특성평가
- ㆍ 저자명
- 이병성,김찬영,한재홍
- ㆍ 간행물명
- 전기전자재료학회논문지
- ㆍ 권/호정보
- 2000년|13권 10호|pp.847-858 (12 pages)
- ㆍ 발행정보
- 한국전기전자재료학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
The aging characteristics of 2 kinds of 3 years field-aged distribution polymer insulators which were dismounted from 5 regions have been investigated by electrical test and material characterization. Although the tan $delta$of specimens prepared from weathershed was increased with surface aging, the tan $delta$and leakage current of real products had no difference between virgin and dismounted ones. Due to the aging, all dismounted polymer insulators had micro-cracks on the surface of weathershed and only the products of manufacturer B showed the reduction of OIT(oxidation induction time). But, there were no differences between virgin and dismounted products in contact angle and chemical structure. Therefore, it can be considered that the aging is only limited on the surface of dismounted polymer insulators and that NMR technique are very useful to evaluate the aging of polymer materials.