- 헬리컬관외 침전 및 적하 열전달 특성에 관한 연구
- ㆍ 저자명
- 황승기,윤상국,김동혁,이승갑
- ㆍ 간행물명
- 설비공학논문집
- ㆍ 권/호정보
- 2001년|13권 4호|pp.225-232 (8 pages)
- ㆍ 발행정보
- 대한설비공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
An experimental study is carried out to investigate the characteristics of heat transfer of outside helical tubes. The main heat exchanger consists of twelve curved columns with each 300mm diameter and the total length of 1.2m copper tube having an outer diameter of 19.05mm with 1.5mm thickness. Water flows down the outside of helical tube, where flow patterns are the vertical film falling flow, immerged flow, and mixed-flow which is the combination of film falling flow and immerged flow. Refrigerant 11 flow the inside of the tube countercurrently. The experimental range of inside flow rate is 1.7~3.2$ell$/min and outside flow rate is 21-33$ell$/min. The results are presented as Nusselt number with corresponding Reynolds number for variety of outside and inside flow rates. The heat transfer rates of the mixed flow are 8 to 56% higher than those of film falling flow or immerged flow only. Interpretation of the results is given on the basis of physical reasoning and the correlation equations.