- 루프 써모사이폰에서 작동유체 충액률과 열유속이 열전달계수의 상관식에 미치는 영향
- ㆍ 저자명
- 장기창,이기우,이영수,유성연
- ㆍ 간행물명
- 설비공학논문집
- ㆍ 권/호정보
- 2001년|13권 6호|pp.462-473 (12 pages)
- ㆍ 발행정보
- 대한설비공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
Due to the coupling between momentum and energy transport theoretical analysis of the loop performance is very complicate, therefore it is necessary that these problems be solved by experimental investigation before applying th loop thermosyphon to heat exchanger design. The evaporator and condenser of the loop thermosyphon were made of carbon-steel, and distilled water was used as working fluid in the experiments. From the experimental data correlations of heat transfer coefficient for evaporator and condenser sections were obtained. For heat fluxes in th range of 13~78kW/$m^2$, the correlation equations of heat transfer coefficients in evaporator and condenser predict the experimental behavior to within $p$pm$5% and;pm20$</TEX>% respectively.