- 대체냉매를 사용한 이원냉동 시스템의 성능에 관한 연구
- ㆍ 저자명
- 박종훈,조금남
- ㆍ 간행물명
- 설비공학논문집
- ㆍ 권/호정보
- 2001년|13권 7호|pp.564-571 (8 pages)
- ㆍ 발행정보
- 대한설비공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
The present study investigated the effect of key parameters on the performance of a cascade system using R-22 and R-23 refrigerants. Experimental data for the cascade system have been compared with simulation results using thermodynamic analysis. The cascade system tested at the evaporating temperature of $-80^{circ}C $ and the condensing temperature of$40^{circ}C $. The key experimental parameters were the evaporating temperature of the HTC(-35, -30, -25, -20, $-15^{circ}C $) and mass flux of the HTC(200, 250, 300kg/$m^2$s). As the evaporating temperature and the mass flux of the HTC were increased respectively, the COP and the refrigerating efficiency were increased and then decreased while the volume flow rate per unit refrigeration capacity showed the opposite trend. The maximum COP and refrigerating efficiency were obtained at the evaporating temperature of the HTC of $-25^{circ}C $ and the mass flux of 250 kg/$m^2$s.