- 발생기 온도저감 및 고온열수 획득을 위한 Hybrid GAX 사이클 해석
- ㆍ 저자명
- 강용태,윤희정,조현철
- ㆍ 간행물명
- 설비공학논문집
- ㆍ 권/호정보
- 2002년|14권 2호|pp.127-133 (7 pages)
- ㆍ 발행정보
- 대한설비공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
The objectives of this paper are to develop an advanced GAX cycle named HGAX (Hybrid Generator Absorber heat exchanger) cycle, and to study the effect of key parameters on the cycle performance and the hot-water temperature from the condenser. New types of the HGAX cycle are developed by adding a compressor between the generator and the condenser- Type C (performance improvement and reduction of the generator temperature) and Type D (Hot-water temperature application). The solution temperature in the generator outlet is reduced to 168$^{circ}C$ with the COP improvement of 19% compared to the standard GAX cycle. The hot-water temperature from the condenser is raised to 106$^{circ}C$ for panel heating (Ondol heating) application.