- 냉매충전량이 모세관 팽창장치를 가진 공기조화기의 성능에 미치는 영향
- ㆍ 저자명
- 최은수,김종배
- ㆍ 간행물명
- 설비공학논문집
- ㆍ 권/호정보
- 2002년|14권 5호|pp.359-364 (6 pages)
- ㆍ 발행정보
- 대한설비공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
A popular type of residential air conditioner is the split system which has two separate units: indoor and outdoor units During field installation of the split system, the potential exists for not setting the charge exactly to the manufacturer´s specifications. The objective of this study is to investigate the effects of the refrigerant charge on the performance of the air conditioner. An air conditioner with capillary tube expansions was tested for various refrigerant charges. The results indicated that the more charge resulted in the more flowrate of the refrigerant. The flowrate of the refrigerant was one of the most important factors to understand the e(sects of the charge on the performance of the air conditioner with capillary tube expansions. Under-charge results in wide region of superheated vapor of the refrigerant in the evaporator, while over-charge results in high temperature of the liquid refrigerant in the evaporator.