- 전력변환 반도체 냉각용 PFC(FC-72) 밀폐형 2상 열사이폰의 열전달 한계에 관한 연구
- ㆍ 저자명
- 박용주,홍성은,김철주
- ㆍ 간행물명
- 설비공학논문집
- ㆍ 권/호정보
- 2002년|14권 9호|pp.725-733 (9 pages)
- ㆍ 발행정보
- 대한설비공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
In this study, the heat transport limitations of a two-phase closed thermosyphon were investigated. For the test, a two-phase closed thermosyphon ($L_t/: 600 mm,;L_e:105mm,;L_a:75mm,;L_c:420mm,;D_o:22.2mm,$ container: copper (inner grooved surface), working fluid: PFC ($C_6F_14$) was fabricated with a reservoir that can change the fill charge ratio. The following was imposed as the factors on the heat transport limitations of a two-phase closed thermosyphon. 1) Fill charge ratio of the working fluid. 2) Tilt angle of the longitudinal axis. From tile experimental data, some results were obtained as follows. When the fill charge ratio was relatively small ($psi$20%), the heat transport limitation occurred about 100W by dry-out limitation. However over 40%, it shelved nearly constant value (500 W) by flooding limitation. The heat transport limitation according to the tilt angle increased smoothly until the tilt angle was <TEX>$60^{circ}$,/TEX>, after then decreased slowly.