- 풍력발전단지의 계통연계 운전이 배전선 보호계전에 미치는 영향
- ㆍ 저자명
- 장성일,김광호
- ㆍ 간행물명
- 전기학회논문지. The transactions of the Korean Institute of Electrical Engineers. A / A, 전력기술부문
- ㆍ 권/호정보
- 2003년|52권 3호|pp.151-157 (7 pages)
- ㆍ 발행정보
- 대한전기학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
Wind farm interconnected with grid can supply the power into a power network not only the normal conditions, but also the fault conditions of distribution network. If the fault happened in the distribution power line with wind fm, the fault current level measured in a relaying point might be lower than that of distribution network without wind turbine generator due to the contribution of wind farm. Consequently, it may be difficult to detect the fault happened in the distribution network connected with wind generator This paper describes the effect of the interconnected wind turbine generators on protective relaying of distribution power lines and detection of the fault occurred in a power line network. Simulation results shows that the current level of fault happened in the power line with wind farm depends on the fault impedance, the fault location. the output of wind farm. and the load condition of distribution network.