- 고층 건물의 실외기실에 위치한 응축기 성능분석
- ㆍ 저자명
- 최석호,이관수,김병순
- ㆍ 간행물명
- 설비공학논문집
- ㆍ 권/호정보
- 2003년|15권 7호|pp.586-594 (9 pages)
- ㆍ 발행정보
- 대한설비공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
The performance of the condenser installed in the air-conditioning plant room of a high-rise building was studied numerically. The effect of the draft direction on the performance of an air-conditioner was analyzed. The on-coil temperature of the condenser was investigated by varying the arrangement and location o( the condenser in the air-conditioning plant room. The performance of an air-conditioner was also evaluated by using COP (coefficient of performance) and CGPI (condenser group performance indicator). The condenser in an air-conditioning plant room should be arranged in such a manner that the fan of the condenser is facing the outside of the building to exhaust the hot air directly, The model by which the condenser is located at the lower-left end of an air-conditioning plant room can prevent the hot air from reentering, and allow indrafting of fresh air. When the direction of draft is to the frontal face of the building, the performance of the condenser above 30th floor is degraded.