- 변압기의 3차원 온도분포 해석
- ㆍ 저자명
- 오연호,송기동,선종호
- ㆍ 간행물명
- 전기학회논문지. The transactions of the Korean Institute of Electrical Engineers. B, 전기기기 및 에너지변환시스템부문
- ㆍ 권/호정보
- 2003년|52권 9호|pp.434-441 (8 pages)
- ㆍ 발행정보
- 대한전기학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
This paper deals with the temperature characteristics according to the cooling medium and the duct size in model transformers. For the analysis and the temperature-rise tests, two 400kVA model transformers have been manufactured. One has been filled with the alpha oil as the cooling medium and constructed the duct sizes of $3 extrm{mm}$ and $5 extrm{mm}$ in the low-voltage and high-voltage windings respectively. The other has been filled the beta oil and the duct sizes were $4 extrm{mm}$ and $6 extrm{mm}$. The temperature-rise tests have been performed by the back-to-back method and the load factor has been controlled the range of 90%∼130%. The temperature values have been measured by the thermocouple and from the sixteen points in each transformer. A commercial CFD program "FLUENT" has been used for the analysis of temperature distribution. The geometry of transformer has been modeled to 3-dimensional by using the hybrid calculation mesh including the radiator. And also, the natural convection velocity has been measured at the oil top position, and compared with the calculated results.