- 물분무노즐의 분사각이 화재실 내부의 온도장에 미치는 영향
- Effect of Spray Angle of Water Mist Nozzle on Temperature Field of Compartment Fire
- ㆍ 저자명
- 김성찬,유홍선,박현태,방기영
- ㆍ 간행물명
- 산업안전학회지
- ㆍ 권/호정보
- 2003년|18권 2호|pp.28-33 (6 pages)
- ㆍ 발행정보
- 한국안전학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
The present study investigates the effect of injection angle of water mist on fire suppression characteristics by numerical simulation. In order to validate the temperature field by numerical simulation, the predicted results are compared with experimental data. It shows that the temperature difference between measurements and predictions are within $10^{circ}C$. Numerical simulations of fire suppression are performed for 4 different injection angle($60^{circ}$, $90^{circ}$, $^120{circ}$, and $180^{circ}$). The global mean temperature over the fire compartment decrease with increasing of spray angle. The result shows that the heat transfer between droplets and gas phase are enhanced with the increasing of spray angle. Near the fire source, temperature field by the wide spray angle is slightly higher than that of narrow injection angle because of direct cooling of fire source.