- 고층 아파트에서 응축기 적층문제 분석
- ㆍ 저자명
- 최석호,이관수,김인규,이동혁
- ㆍ 간행물명
- 설비공학논문집
- ㆍ 권/호정보
- 2004년|16권 9호|pp.796-803 (8 pages)
- ㆍ 발행정보
- 대한설비공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
The stack effect of a new type condenser installed in a high-rise apartment building was studied numerically A sirocco fan is introduced to the new type condenser instead of an axial flow In. The new type condenser intakes the cold air through the lower inlet and exhausts the hot air through the upper outlet. The effects of the building height and frontal wind on the performance of an air-conditioner were analyzed. The performance of an air-conditioner was evaluated by using COP (coefficient of performance) and CGPI (condenser group performance indicator). the hot air was exhausted by the new type condenser at an angle of 50$^{circ}$ from the outer wall of the building. If there was no draft, the new type condenser installed in the high-rise apartment building had a good performance and its performance on each floor is not influenced by the stack effect. It is shown that the efficiency of the air-conditioner installed in several floors below the top floor decreased when the frontal wind velocity was greater than 8 m/s.