- 온도 성층축열조 가시화 및 실증분석에 관한 고찰
- ㆍ 저자명
- 이영수,이상남,김종률,Lee. Young-Soo,Lee. Sang-Nam,Kim. Jong-Ryul
- ㆍ 간행물명
- 설비공학논문집
- ㆍ 권/호정보
- 2005년|17권 11호|pp.990-997 (8 pages)
- ㆍ 발행정보
- 대한설비공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
The stratified effect was investigated with three different types of diffuser shape in a thermal storage tank with variation of diffuser diameter, velocity, Froude number etc. Its effect was estimated by the degree of stratification. No matter of diffuser diameter and shape, the degree of stratification was the best as the Froude number gets closer to 1. In the case of a curved diffuser, when its diameter is a quarter of tank diameter and ejection velocity in a diffuser is approximately 0.2 m/s, the Froude number was almost 1. In the case of a flatted diffuser, when ejection velocity was 0.05 m/s, the Froude number was 1.5. Both cases which Froude number were nearer 1, showed the good degree of stratification.