- 빙축열 시스템 냉동기 성능 및 축열밀도 현장측정 기법연구
- ㆍ 저자명
- 신영기,양훈철,태춘섭,조수,김영일,Shin. Younggy,Yang. Hooncheul,Tae. Choon-Seob,Cho. Soo,Kim. Youngil
- ㆍ 간행물명
- 설비공학논문집
- ㆍ 권/호정보
- 2005년|17권 12호|pp.1204-1209 (6 pages)
- ㆍ 발행정보
- 대한설비공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
In-situ measurement was made to evaluate chiller performance and thermal storage density of an ice thermal storage system. The system belonged to a big hotel and the measurement was conducted during late October. Owing to very small cooling load, the data logging was possible for a single thermal storage cycle. However, operation history of the chiller showed a relatively good spectrum of data for performance evaluation. COP and thermal storage density were calculated. The COP at full load was about 4.07, which was lower than $4.8~6.4$ of new chillers. The measured storage density was about $10.9RT-h/m^3;(=152MJ/m^3)$, which also was lower than a criterion of normal performance $(above;13.0RT-h/m^3;or;181MJ/m^3)$. The study result provides technical basis for quantitative ESCO business scenario.