- 열전모듈을 이용한 냉방기의 최적 운전조건에 관한 실험적 연구
- ㆍ 저자명
- 황준,강병하,Hwang. Jun,Kang. Byung-Ha
- ㆍ 간행물명
- 설비공학논문집
- ㆍ 권/호정보
- 2006년|18권 1호|pp.66-72 (7 pages)
- ㆍ 발행정보
- 대한설비공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
This article presents the optimal operation of an air conditioner using thermoelectric modules. A prototype of air conditioner using four thermoelectric modules has been designed and built. The system performance with evaporative cooling for hot side of the module are studied in detail for several operating parameters, such as input power to the thermoelectric module, fans and pump. It is found that the optimal input voltage to the thermoelectric module and pump is selected for the best system performance based on the cooling capacity and the COP at a given operating condition. It is also found that both the cooling capacity and COP of a system is increased with an increase in the input power to fans. The cooling performance could be improved when the ambient temperature is increased and the relative humidity is decreased since the evaporative cooling at the hot side has been increased