  • Leakage Current Waveforms of Outdoor Polymeric Insulators and Possibility of Application for Diagnostics of Insulator Conditions
  • Leakage Current Waveforms of Outdoor Polymeric Insulators and Possibility of Application for Diagnostics of Insulator Conditions
저자명
Suwarno. Suwarno
간행물명
Journal of electrical engineering & technology
권/호정보
2006년|1권 1호|pp.114-119 (6 pages)
발행정보
대한전기학회
파일정보
정기간행물|ENG|
PDF텍스트
주제분야
기타
이 논문은 한국과학기술정보연구원과 논문 연계를 통해 무료로 제공되는 원문입니다.
서지반출

기타언어초록

This paper reports the investigation results on the leakage currents (LC) on polymeric outdoor insulators. The samples used were EPDM (ethylene prophylene diene monomer) insulators used at 20 kV distribution lines. AC voltage was applied and the LC waveforms were measured under various environmental conditions (humidity and pollution). Digital data of the LC was transferred from a digital storage oscilloscope to a computer for further analysis. The LC waveform parameters such as magnitude and harmonic content (as indicated by the total harmonic distortion (THD)) were analyzed. The experimental results showed that 3rd, 5th and 7th harmonics and higher odd harmonics were observed for symmetrical-distorted LC waveforms while for unsymmetrical-distorted LC waveforms, odd and even harmonics were observed. The LC analysis indicated that there are 5 stages of insulator conditions from normal condition up to flashover correlated with different kind of LC waveforms. The results also showed that in general the magnitude of LC was good enough to show the condition of the insulators. However, under discharge condition (for example as a result of dry band arching) the LC magnitude should be combined by the THD to show a better correlation with the insulator condition. The product between THD and LC magnitude may be used as a diagnostic parameter.