- 증발기와 응축기 온도변화에 따른 R22 대체냉매 R290 및 R1270의 성능평가
- ㆍ 저자명
- 백인철,박기정,심윤보,정동수,Baek. In-Cheol,Park. Ki-Jung,Shim. Yun-Bo,Jung. Dong-Soo
- ㆍ 간행물명
- 설비공학논문집
- ㆍ 권/호정보
- 2006년|18권 10호|pp.761-767 (7 pages)
- ㆍ 발행정보
- 대한설비공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
In this study, performance of 2 pure hydrocarbons R290 and R1270 was measured in an attempt to substitute R22 under 3 different temperature conditions. They were tested in a refrigerating bench tester with a hermetic rotary compressor. The test bench provided about 3.5 kW capacity and water and water/glycol mixture were employed as the secondary heat transfer fluids. All tests were conducted under the same external conditions resulting in the average saturation temperatures of $7/45^{circ}C$ and $-7/41^{circ}C$ and $-21/28^{circ}C$ in the evaporator and condenser, respectively. Test results show that the coefficient of performance (COP) of these refrigerants is up to 11.54% higher than that of R22 in all temperature conditions. Compressor discharge temperatures were reduced by $14{sim}31^{circ}C$ with these fluids. There was no problem with mineral oil since the mixtures were mainly composed of hydrocarbons. The amount of charge was reduced up to 58% as compared to R22. Overall, these fluids provide good performance with reasonable energy savings without any environmental problem and thus can be used as long term alternatives for residential air-conditioning and heat pumping application.