- 복사냉각 시스템에서 커버의 영향
- ㆍ 저자명
- 변기홍,Byun. Ki-Hong
- ㆍ 간행물명
- 설비공학논문집
- ㆍ 권/호정보
- 2007년|19권 11호|pp.797-802 (6 pages)
- ㆍ 발행정보
- 대한설비공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
The effects of window cover on the performance of the plate type radiant cooling test system are studied. The cover materials tested are 2mm, 1mm, 0.7mm glass, Cokin 007 filter, and PVC film. The measurements are performed during the September nights of 2005 at the rooftop of the building in Seoul. The equivalent height of the building is about a building with twelve floors. The radiant cooling performance of the black painted and aluminum film coated plate are compared under no cover condition. Also the results are compared when the system has cover over the plate. In general, the covers reduce the radiant cooling temperature differences during the nighttime. Among these covers, the PVC film cover shows the best performance. In some cases, the plate with PVC film cover shows lower temperatures than the system without cover.