- 고분 공조시스템의 운전특성 및 제습부하에 관한 연구
- ㆍ 저자명
- 박진양,고석보,전희호,전용두,이금배,Park. Jin-Yang,Ko. Seok-Bo,Jun. Hee-Ho,Jun. Yong-Du,Lee. Kum-Bae
- ㆍ 간행물명
- 설비공학논문집
- ㆍ 권/호정보
- 2007년|19권 3호|pp.253-262 (10 pages)
- ㆍ 발행정보
- 대한설비공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
Although the importance of good conservation of historical sites including ancient royal tombs is well aware, still not much attention has been paid for facilities to realize it. There are numerous ancient royal tombs spread in Korean peninsula which are opened and some of them are selectively on display for public access. However, the conservation measures of these sites have not been seriously investigated. Even the level of understanding of the underground environment of tombs is not satisfactory. In the present study, we focus on the dehumidification loads to maintain appropriate conservation conditions in terms of temperature and humidity. Two experimental tombs different in size were built in KNU (Kongju National University) campus with the dimensions ($L{ imes}W{ imes}H$) of $1.0m{ imes}2.8m{ imes}1.0m;and;1.3m{ imes}3.0m{ ime}1.2m$, respectively, HVAC systems are installed to maintain a suitable condition for conservation, i.e., $22{pm}2^{circ}C$ in temperature and $55{pm}5%$ in relative humidity. The condensed water are measured to estimate the dehumidification loads while the temperature and the humidity inside the tombs were maintained within the specified range.