- 군 병영시설의 실내 공기질 평가 및 특성
- ㆍ 저자명
- 김석봉,정상조,백상호,김태욱,박영준,Kim. Suk-Bong,Jeong. Sang-Jo,Baek. Sang-Ho,Kim. Tae-Wook,Park. Young-Jun
- ㆍ 간행물명
- 韓國軍事科學技術學會誌
- ㆍ 권/호정보
- 2007년|10권 4호|pp.168-175 (8 pages)
- ㆍ 발행정보
- 한국군사과학기술학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
In this study, the Indoor Air Quality(IAQ) in military barracks is evaluated and its characteristics is discussed as well. The military barracks of R.O.K Army are categorized into three types and the IAQ in these individual facilities is measured for 24 hours both in summer and winter. Test results show that the particulate matters($PM_{10}$) and carbon dioxide($CO_2$) were the main causes contaminating IAQ in military barracks. While $CO_2$ can be purified by ventilation, adequate facilities have to be installed in case of the new type of combination barracks to remove $PM_{10}$. In addition, to improve the living condition of military barracks and to recover IAQ in new combination style barracks which is planned to complete by 2011, a standard or law regulating IAQ in military barracks has to be established.