- 전력케이블 접속재 XLPE/EPDM 계면의 부분방전 특성
- ㆍ 저자명
- 조경순,홍진웅,Cho. Kyung-Soon,Hong. Jin-Woong
- ㆍ 간행물명
- 전기전자재료학회논문지
- ㆍ 권/호정보
- 2007년|20권 9호|pp.780-786 (7 pages)
- ㆍ 발행정보
- 한국전기전자재료학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
This paper describes the influence on partial discharge characteristics of defects at the model XLPE/EPDM interfaces of power cable joints. The defects of void and copper which could inadvertently be present at the joint interface. We measured ${Phi}-n,;{Phi}-q$ patterns by a computer-aided partial discharge measuring system. Several parameters i, e, maximum discharge $q_{max}$ [pC], average discharge q [pC/cycle], and average angle of discharge ${Theta}g$ [deg] were found to depend upon the defect type varying applied voltage. As the result of time evaluation, partial discharges are small different at copper defects, but is decreasing obviously about 20 minutes at void defect. It considered that difference of magnitude of total positive discharge of Q+ [pC] and total negative discharge of Q- [pC] is SPMD(swarming pulsive micro discharges).