- 가스터빈 발전기 회전자 권선의 절연상태 평가
- ㆍ 저자명
- 김희동,김병래,Kim. Hee-Dong,Kim. Byeong-Rae
- ㆍ 간행물명
- 전기학회논문지= The Transactions of the Korean Institute of Electrical Engineers
- ㆍ 권/호정보
- 2008년|57권 10호|pp.1818-1821 (4 pages)
- ㆍ 발행정보
- 대한전기학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
Several off-line diagnostic tests which include the insulation resistance(IR), polarization index(PI), low-voltage AC, and recurrent surge oscillograph(RSO) tests were performed to assess the condition of generator rotor windings. The low-voltage AC and the RSO tests were performed on the gas turbine generator rotor winding to detect shorted turns. Before intentionally applying artificial shorted faults, it was confirmed by the low voltage AC and the RSO tests that the winding was in sound condition. For simulated shorted rotor winding turns, the RSO test detected the fault in the winding. The RSO test was capable of identifying the number and pole location of the shorted turns for a number of simulated shorted coils.