단일동조 수동고조파필터 설계시의 동조계수(δ) 및 양호도(Q)값 연구
[STEP1]서지반출 형식 선택
파일형식
@
서지도구
SNS
기타
[STEP2]서지반출 정보 선택
  • 제목
  • URL
돌아가기
확인
취소
  • 단일동조 수동고조파필터 설계시의 동조계수(δ) 및 양호도(Q)값 연구
저자명
조영식,차한주,Cho. Young-Sik,Cha. Han-Ju
간행물명
전기학회논문지. The Transactions of the Korean Institute of Electrical Engineers. P
권/호정보
2010년|59권 1호|pp.64-70 (7 pages)
발행정보
대한전기학회
파일정보
정기간행물|
PDF텍스트
주제분야
기타
이 논문은 한국과학기술정보연구원과 논문 연계를 통해 무료로 제공되는 원문입니다.
서지반출

기타언어초록

This paper presents how to decide on tuning factor(${delta}$) and quality factor(Q) values in design of single-tuned passive harmonic filters. Tuning factor(${delta}$) and quality factor(Q) values have to consider before decision on circuit parameters of passive filters. A Study on these two value has not been scarcely performed and only experienced values has been used in passive harmonic filter design by far. As a experienced value, in cases of 5th and 7th filter, tuning factor(${delta}$) is about 0.94 and 0.96 respectively and quality factor(Q) is, in all cases of, 50. If Single-tuned passive harmonic filter will be off-tuned, performance of filter will be decreased steeply and occur to parallel resonance between system reactance and filter capacitance. Therefore During the operation, In order not to off-tuning, Filter must be tuned at former order than actual tuning order. This is the same that total impedance of filter must have a reactive impedance. In this paper, Tuning factor(${delta}$) is decided via example of real system and using the bode-plot and then performance of filters confirmed by filter current absorbtion rate. And Quality factor(Q) decided using the bode plot in example system and then performance of filters confirmed by filter current absorbtion rate also, which makes a calculated filter parameters to satisfy IEEE-519 distortion limits. Finally, Performance of the designed passive harmonic filter using the tuning factor(${delta}$) and quality factor(Q) values, decided in this paper is verified by experiment and shows that 5th, 7th, 9th, 11th and 13th current harmonic distortions are decreased within IEEE-519 distortion limits, respectively.