- 축열조를 이용한 냉매과냉각 시스템의 전력수요관리 효과에 대한 연구
- ㆍ 저자명
- 김정배,이은지,이동원,Kim. Jeong-bae,Lee. Eun-Ji,Lee. Dong-Won
- ㆍ 간행물명
- 설비공학논문집
- ㆍ 권/호정보
- 2010년|22권 12호|pp.845-851 (7 pages)
- ㆍ 발행정보
- 대한설비공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
This study was experimentally performed to find the effects of refrigerant subcooling in the refrigeration system and to propose how to get the efficient use of energy. A refrigerant-subcooling refrigeration system consisted of a typical single vapor-compression refrigeration cycle, a subcooler, and an ice storage tank. The degree of subcooling at the exit of the condenser can be increased by the heat transfer between the subcooler and the ice storage tank. The cold heat in the ice storage tank was stored by using the refrigeration cycle during night time and then used to absorb the heat from the subcooler during daytime. The cooling capacity and COP of this system were higher than those of the conventional system due to the increase in the degree of subcooling. Typically, the refrigerant-subcooling system showed superior performance to the conventional refrigeration system and would also contribute to load leveling.