- 삼선 지락사고 발생시 매트릭스형 한류기용 리액터의 전자장 분포 해석
- ㆍ 저자명
- 정동철,한태희,Chung. Dong-Chul,Han. Tae-Hee
- ㆍ 간행물명
- 전기학회논문지= The Transactions of the Korean Institute of Electrical Engineers
- ㆍ 권/호정보
- 2011년|60권 2호|pp.459-463 (5 pages)
- ㆍ 발행정보
- 대한전기학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
In this paper we reported the characteristics of 1 line, 2 lines and 3 lines-to-ground fault of matrix-type SFCLs (MFCLs) and the electromagnetic field distribution of reactors for MFCLs under the same cases of ground faults. To do this, we fabricated MFCLs with 6 reactors for 3 phases. Each reactor had the length of 270 mm and diameter of 80 mm. 6 reactors were made by Bakelite. We reported experimental results, including fault currents, fault voltages and magnetic field distribution according to phase differences between each phase. We confirmed that experimental results will be useful in next future plan for real power grid.