- 패시브환기외피의 통기 및 열성능에 관한 실험적 연구
- ㆍ 저자명
- 윤성환,이태철,강정식,Yoon. Seong-Hwan,Lee. Tae-Cheol,Kang. Jung-Sik
- ㆍ 간행물명
- 설비공학논문집
- ㆍ 권/호정보
- 2011년|23권 11호|pp.711-717 (7 pages)
- ㆍ 발행정보
- 대한설비공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
In this study, 5 types of PVS(Passive ventilation system) units are made and experimented its ventilation performance, thermal performance according to open rate and hole diameter of perforated aluminum plane. Results are as follows. 1) The ventilation performance increases approximately 50~70% according by the open rate of PVS increasing. Also, the ventilation performance increases about 2%~12% according by the hole diameter of PVS increasing. 2) In winter temperature/pressure condition(in : $20^{circ}C$, out : $-2^{circ}C/{Delta}P$ : 0.2~5.0Pa) the temperature of inflow air decreases according by the open rate of PVS increasing. Heat gain performance decreases 10.1%, 25.6% when open rate increases 3) In the same condition, Heat gain performance decreases 18.3%, 18.8% according by the hole diameter of PVS increasing.