- 누전차단기의 트립 동작시간 분석을 통한 전류·시간적(積) 개선
- ㆍ 저자명
- 김주철,이상중,Kim. Ju-Chul,Lee. Sang-Joong
- ㆍ 간행물명
- 照明·電氣設備學會論文誌
- ㆍ 권/호정보
- 2012년|26권 12호|pp.44-49 (6 pages)
- ㆍ 발행정보
- 한국조명전기설비학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
The earth leakage circuit-breakers installed to protect the human body against electrical shock have conventionally had a sensitivity current of 30 mA and an operating time of 30 ms or less. No reviews are found, however, on the operating time of the current conducting through the human body due to the electrical shock or ground fault. This paper measures the trip-operating time against the earth leakage under the condition of increased current as well as under the condition of rated sensitivity current of the earth leakage circuit-breakers. Further measurement with a prototype model showed an improved operating time of 16 ms or less under the condition of rated sensitivity current. It is expected that development of circuit-breakers with higher safety is possible if the performance of the electronic circuit can be improved.