- 과냉각 축냉시스템을 적용한 쇼케이스의 운전 특성에 대한 실험적 연구
- ㆍ 저자명
- 이동원,김정배,Lee. Dong-Won,Kim. Jeongbae
- ㆍ 간행물명
- 한국태양에너지학회 논문집
- ㆍ 권/호정보
- 2012년|32권 6호|pp.22-28 (7 pages)
- ㆍ 발행정보
- 한국태양에너지학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
The purpose of this study was to show how tomaintain high efficiency and to use reasonably when being applied the cold-heat storage systems to the showcase. An experimental study was performed to manufacture the showcase system in a laboratory. Comparing the result at general operation condition with that of the new condition using ice storage system, this study showed the effects of the refrigerant sub-cooling, and with using inverter. Using ice storage system, the ice making process was operated during midnight being not needed the cooling of the showcase through the continuous running of the condenser unit. And then, the refrigerant was sub-cooled using the stored cold-heat after being discharged from the air cooling condenser during the day time. Through the experiments, the load transfer rate for the showcase using inverter and ice storage was estimated about 30.0%. And showed that the total power consumption of the showcase with inverter could be reduced about 37% than that of the showcase without inverter.