- LabView 기반 부분방전 분석장치의 설계 및 제작
- ㆍ 저자명
- 차현규,이정윤,박대원,길경석,Cha. Hyeon-Kyu,Lee. Jung-Yoon,Park. Dae-Won,Kil. Gyung-Suk
- ㆍ 간행물명
- 전기전자재료학회논문지
- ㆍ 권/호정보
- 2012년|25권 3호|pp.229-235 (7 pages)
- ㆍ 발행정보
- 한국전기전자재료학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
This paper dealt with the fabrication of a partial discharge (PD) analyzer for insulation diagnosis of power facilities like transformers, cables and gas-insulated switchgears. An analytic algorithm for the phase (${phi}$), the magnitude (q), and the pulse count (n) of PD pulse was designed and a time-frequency (TF) map algorithm was applied in the system to eliminate noises by analyzing the time and the frequency component of signals. All the algorithms were operated by a LabView graphical program. The detection circuit consists of a coupling capacitor, a detection impedance, and a low noise amplifier. A plane-plane and a point-plane electrode system were fabricated to simulate different types of insulation defects. In the experiment, we could easily understand the characteristics of PD pulses using the prototype PD analyzer.