- 광학렌즈 AR 코팅에 따른 폴리머애자에서의 방전 자외선 강도 비교
- ㆍ 저자명
- 김영석,송길목,방선배,김종민,최명일,Kim. Young-Seok,Shong. Kil-Mok,Bang. Sun-Bae,Kim. Chong-Min,Choi. Myeong-Il
- ㆍ 간행물명
- 照明·電氣設備學會論文誌
- ㆍ 권/호정보
- 2012년|26권 4호|pp.35-40 (6 pages)
- ㆍ 발행정보
- 한국조명전기설비학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
In this study, the ultraviolet (UV) intensity of polymer insulator was measured using the Anti-Reflective (AR) coating lens on the occurrence of corona discharge. The UV intensity was compared before and after the AR coating. Under the 200-260[nm] of UV lens, the reflection rate before AR coating was 7.5~5.5[%] with 85-89[%] of transmission rate. After AR coating, however, the reflection rate decreased to 1.3~1.22[%] with improved transmission (97.4~97.6[%]). Then, the UV intensity by distance was measured in the polymer insulator. According to the measurement, the UV intensity increased 6.5 times at 37.5[%] of Vm/Vbd with 5[m] of distance. As distance increased, the growth rate declined. As high voltage increased, in addition, AR coating was less effective due to the count error caused by the UV sensor pulse signal overlap. Therefore, it appears that it would be more effective to detect corona discharge with 5[m] or less of distance at diagnosis of power facilities by AR coating and UV sensor sensitivity.