- 외장재 설치 공간의 화재확산 차단에 관한 연구
- ㆍ 저자명
- 민세홍,윤정은,김미숙,Min. Se-Hong,Yun. Jung-Eun,Kim. Mi-Suk
- ㆍ 간행물명
- 대한안전경영과학회지
- ㆍ 권/호정보
- 2012년|14권 2호|pp.83-89 (7 pages)
- ㆍ 발행정보
- 대한안전경영과학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
In this study, FDS fire simulation experiments and measured wind speed by applying the exterior installation portion for blocking the spread of the fire was investigated. As a result, aluminum composite panels installed in the lower and the upper part of the panel to remove all the lower side, and then the maximum wind speed 0.24 m/s and the upper side 0.58 m/s were measured. In the FDS, the measured wind speed difference air currents are approximately 3.7 times in 12 seconds, the occurrence of 17 seconds early moment wind 2.2 m/s was measured from. Before and after the fire occurred in early of the air velocity about 39 seconds was 3.5 times difference. Such air currents caused by the temperature of the building but also by the building height was found. Turbulent flame of fire by expanding the vertical extent of damage become greatly important factor. Therefore, through the exterior installation portion of the block that can delay the spread of fire is expected that this should be taken.