- 실내 부하조건에 따른 바닥공조 시스템의 에너지 성능 평가
- ㆍ 저자명
- 윤성훈,장향인,김경아,유기형,서승직,Yoon. Seong-Hoon,Jang. Hyang-In,Kim. Kyung-Ah,Yu. Ki-Hyung,Suh. Seung-Jik
- ㆍ 간행물명
- 설비공학논문집
- ㆍ 권/호정보
- 2013년|25권 1호|pp.14-19 (6 pages)
- ㆍ 발행정보
- 대한설비공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
The present study has been conducted for evaluating and comparing the performance of the underfloor air distribution system(UFAD) and the ceiling based air distribution system(CBAD) under cooling condition. Simulations and experiments were carried out for verifying the model by TRNSYS program about UFAD and CBAD. The results of simulation for various conditions of thermal load are summarized as followings. UFAD had an advantage for making thermal comfort because of lower temperature of the floor surface. Moreover, UFAD showed lower fan power about 30~50% than CBAD under the same conditions of thermal load. The energy saving rates of UFAD were increased to 17.7% in proportion to the thermal load on unoccupied zone(lighting). Ultimately, additional investigations should be done for analyzing optimized operating conditions of UFAD with considering the thermal performance of building envelop and the thermal load.