- 3전극과 4전극 전위강하법으로 측정한 대지저항률의 비교
- ㆍ 저자명
- 이복희,김기복,Lee. Bok-Hee,Kim. Ki-Bok
- ㆍ 간행물명
- 照明·電氣設備學會論文誌
- ㆍ 권/호정보
- 2013년|27권 2호|pp.95-101 (7 pages)
- ㆍ 발행정보
- 한국조명전기설비학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
This paper presents the comparison of the earth resistivity obtained from the measurements made with the three-electrode and four-electrode fall-of-potential techniques. The ${ ho}-a$ curve obtained from Wenner four-electrode method in undisturbed earth is in good agreement with the ${ ho}-l$ curve obtained from the three-electrode method based on the fall-of- potential method. However, The ${ ho}-a$ curve in disturbed earth with moisture and freezing is significantly different with the ${ ho}-l$ curve. The ${ ho}-a$ curve is considerably sensitive to the freezing and the moisture present in the earth surface compared to the ${ ho}-l$ curve. Thus to determine the actual earth resistivity, it is necessary to take into account the earth surface conditions when measuring the earth resistivity.