- 간접 냉동 시스템용 2차 냉매의 열전달과 압력강하 특성
- ㆍ 저자명
- 오후규,손창효,조환,이문빈,전민주,Oh. Hoo-Kyu,Son. Chang-Hyo,Jo. Hwan,Yi. Wen-Bin,Jeon. Min-Ju
- ㆍ 간행물명
- 한국동력기계공학회지
- ㆍ 권/호정보
- 2013년|17권 4호|pp.45-50 (6 pages)
- ㆍ 발행정보
- 한국동력기계공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
This paper presents the comparison of heat transfer and pressure drop of various secondary refrigerants (single-phase and two-phase) in the indirect refrigeration system. The main results were summarized as follows: In case of heat transfer, it is useful to use secondary refrigerants in low evaporating temperature region and the heat transfer coefficient of single-phase is larger than two-phase secondary refrigerants. In case of pressure drop, it is useful to use secondary refrigerants in high evaporating temperature region and the pressure drop of two-phase is smaller than single-phase secondary refrigerant. Also, $CO_2$ is the best useful because pressure drop of $CO_2$ among the secondary refrigerants is the smallest.