- 지하수 수위가 개방형 지열시스템 성능에 미치는 영향에 관한 연구
- ㆍ 저자명
- 김진상,남유진,Kim. Jinsang,Nam. Yujin
- ㆍ 간행물명
- 한국지열에너지학회논문집
- ㆍ 권/호정보
- 2013년|9권 3호|pp.1-10 (10 pages)
- ㆍ 발행정보
- 한국지열에너지학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
Open loop geothermal heat pumps have great potential where the groundwater resources are sufficient. Performance of open loop geothermal heat pump systems is considered higher than that of ground source heat pumps. Head and power calculation of submersible pumps, heat pump units, and piping are numerically based on regression data. Results shows that the system performance drops as the water level drops, and the lowest flow rates generally achieve the highest system COPs. The highest achievable cooling system COPs become 6.34, 6.12, and 5.95 as the groundwater levels are 5m, 15m, and 25m. The highest heating system COPs also become 4.59, 4.37, and 4.20. Groundwater level and submersible pump selection greatly influence the system performance of open loop geothermal heat pumps. It needs to be analysed during the design process of open loop geothermal heat pump system, possibly with analysis tools that include wide range of pump product data.