- 서버 컴퓨터의 발열량이 변화한 경우의 데이터센터 내의 기류 및 온도분포 특성에 대한 연구
- ㆍ 저자명
- 장현재,김제영,Chang. Hyun-Jae,Kim. Je-Young
- ㆍ 간행물명
- 설비공학논문집
- ㆍ 권/호정보
- 2014년|26권 3호|pp.108-114 (7 pages)
- ㆍ 발행정보
- 대한설비공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
On a large scale of data center, heat generation rates from sever computers occupy almost the entire cooling load of the building, and it is gradually increasing. The efficiency of air distribution system in data centers can be affected by heat generation rates of server computers. In this study, the distributions of airflow and temperature in a data center have been investigated by CFD simulations under various conditions of heat generation rates for server computers. From the results, air around the cold aisle which has high temperature flows tremendously into the cold aisle according to the increase of heat generation rates for server computers and the air temperature in the cold aisle becomes higher. The SHI (supply heat index) and RHI (return temperature index) show almost similar values to the cases study because the air inflow rates to server computers increase with the heat generation rates of server computers.