- 저온창고에서 냉동기 응축폐열을 이용한 제상시스템 성능평가
- ㆍ 저자명
- 박천완,이동규,임관빈,강채동,Park. Chunwan,Lee. Donggyu,Im. Kwanbin,Kang. Chaedong
- ㆍ 간행물명
- 설비공학논문집
- ㆍ 권/호정보
- 2014년|26권 2호|pp.72-78 (7 pages)
- ㆍ 발행정보
- 대한설비공학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
In a cold chain, the refrigerator is also employed for defrosting, by using an electric heater, which consumes 15% of the power for the system operation. In this study, the condensation heat of the refrigerant was suggested as the heat source of defrosting heat, instead of that from an electric defrost heater. The heat for defrosting was stored to a phase change material (PCM, NMP : $52^{circ}C$) in thermal storage, and was periodically supplied to the evaporator by a circulation loop of brine. As a result, a defrost time by the PCM was obtained that was less than or equal to that by the electric heater. Moreover, power consumption during defrosting was saved by up to 99% of that of the electric heater.