- 6.6 kV 전동기 고정자 권선의 절연진단과 절연내력 평가
- ㆍ 저자명
- 김희동,공태식,Kim. Hee-Dong,Kong. Tae-Sik
- ㆍ 간행물명
- 전기학회논문지= The Transactions of the Korean Institute of Electrical Engineers
- ㆍ 권/호정보
- 2014년|63권 6호|pp.780-785 (6 pages)
- ㆍ 발행정보
- 대한전기학회
- ㆍ 파일정보
- 정기간행물| PDF텍스트
- ㆍ 주제분야
- 기타
To assess the deterioration condition of stator insulation, diagnostic and AC dielectric strength tests were performed on five high voltage (HV) motors (2,000 HP, 6.6 kV) for boiler feed-water pump (BFP). Two HV motors for BFP were installed per unit. Following the long term rewinding program, the diagnostic test was performed on five 6.6 kV motors during the planning maintenance period. After completing diagnostic test, AC dielectric strength test was done on the stator windings of HV motors. The AC dielectric strength test was conducted at 15 kV for one minute. Dielectric strength test and diagnostics test results confirmed that the stator insulation was judged to be in serviceable condition in the five 6.6 kV motors.